By Christopher W. Carlson, P.E., SECB

Chris Has been practicing structural engineering for over 24 years and is focused on the evaluation and repair of defects on existing buildings. He is the chief structural engineer with ETC, Inc. and oversees the structural staff activities.

For many visitors, the parking garage creates the first impression of a building. Performing routine maintenance provides a cleaner, safer, more welcoming atmosphere. However, the parking garage is often the least maintained part of a facility even though they are often exposed directly to the weather unlike the rest of the building. Therefore, they need more attention because the garage is not a destination, just a trans­fer point. It is also “painful” to disrupt the status-quo and have a hundred or more residents move their cars out of their spaces for a few days. Just the thought of this endeav­ or could make you cringe. After all, if there were plenty of parking spaces nearby, you wouldn’t need a parking garage.

Maintenance is intended to delay future major garage repairs by performing smaller tasks in a periodic manner before they degrade into bigger issues. Parking indus­try trade associations and manufacturers of products used to protect parking garag­es from deterioration offer many resources to aid in developing a routine maintenance plan tailored to your garage. Experts sug­gest that you should budget at least $35 to as much as $500 per space, per year, for annu­ al maintenance, as well as to help put mon­ey aside for that day when a major repair is needed.

Garages contain many systems that must be maintained besides the structure, often in­cluding HVAC, electrical, plumbing/drain­ age, elevators, landscaping, lobbies, and access/security. new-deck-coating What Statement Does Your Garage Make?

Several items to consider when developing your maintenance plan for each system are listed below.

Structure maintenance plans are primarily aimed at protecting the concrete and steel from water and deicing chemical attack. The following major items should be includ­ed.

  • Flush and clean driving surfaces and drains to remove dirt and deicing chem­icals at least twice a year (spring and fall). This may include hydro jetting of the drainpipes to ensure they are flowing free­ly. Include all levels of the garage, not just the outdoor surfaces where deicing chem­icals have been applied. Don’t forget the stairways. Once a year, check the moisture protec­tion systems, such as membrane deck coatings for excessive wear, tears, bubbling, and ripping. Check sealant joints for debonded areas. Look for unsealed cracks that can allow water to migrate through the concrete. A telltale sign that the membrane is damaged is if water and minerals are dripping from the slab above onto cars.
  • In the spring, check the expansion joints as they are often damaged during snow plowing
  • Several times a year, inspect for spalled concrete, corrosion stains, and white min­eral deposits. At the same time look for life safety concerns such as damaged cable barriers, handrails that wobble, and trip hazards.
  • Recoat your deck membrane at least every five years to help ward off This can be a full recoat or a targeted coating of the drive aisles, turning areas, and ramps where the membrane is subjected to the most abuse.

new-deck-coating What Statement Does Your Garage Make?

  • Retain experts to perform an in-depth ga­ rage evaluation/audit every three to five years. This inspection might need to be performed yearly if the garage is over ten years old and has been neglected. 

Maintenance items to be performed on the other systems usually include the following:

  • General cleaning, painting, door and hardware repairs, and elevator mainte­nance.
  • Electrical equipment- light fixture clean­ ing and replacement. Check emergency lights. Electrical conduits that have cor­roded through must be replaced. 
  • Parking access controls, security, and CCTV systems usually are upgraded as technology advances
  • Ventilation systems must be maintained. Few realize that carbon monoxide detectors need to be replaced about every five
  • Painting- Fire sprinkler system pipes often sweat during times of high humidity and can Metal stair treads corrode over time.
  • Check the condition of aesthetic items such as signage, striping, and
  • Water intrusion through perimeter walls into underground garages should be addressed as they are found.

Do not rely on your static reserve study to determine when the ga­rage system needs to be repaired or replaced, things change over time, and the current condition might dictate otherwise.

Many problems can be inexpensively remedied if addressed in a timely manner.

Neglecting maintenance or making improper repairs will contribute to shortening the life of the structure and/or the system. Start a maintenance program today and have your garage make a positive statement.

What Statement Does Your Garage Make?

Maryland
7165 Columbia Gateway Drive
Columbia, Maryland  21046
phone: 410.312.4761
fax: 410.312.0482

Northern Virginia
46040 Center Oak Plaza
Suite 100
Sterling, Virginia 20166
phone: 703.450.6220
fax: 703.444.2285